Generator Set | |
Rating Prime | 182 ekW (228 kVA) |
Frequency | 60 Hz |
Voltage | 120 - 600 V |
Rating Standby | 200 ekW (250 kVA) |
Engine | |
Engine | Cat C7.1 |
Fuel | Diesel |
Dimensions | |
Height - Without Trailer | 78.5 in |
Length - Without Trailer | 162.2 in |
Width - Without Trailer | 62.8 in |
Weight with Lube Oil and Coolant, Without Trailer | 8432 lb |
Fuel Consumption | |
100% Load 60Hz | 14.7 gal/hr |
75% Load 60Hz | 10.8 gal/hr |
50% Load 60Hz | 7.4 gal/hr |
Noise rating (with enclosure) | |
Sound Power @ 7 meters (23 feet) @ All Ratings | 72 dB(A) |
Rental ready. Retail Optimized (Option)
Robust, durable product with a range of rental ready features to meet job requirements and applications.
Option for open genset to meet retail customer needs.
Fuel/Emissions Strategy
Meets U.S. EPA Tier 4 Final emission standards and CARB certified for non-road mobile applications at all 60 Hz ratings
Cat C7.1 Diesel Engine
Industry proven reliability
CAT EMCP4.2B digital controls
Easy to use digital controls
Cat LC Series Generator
Integrated voltage regular for fast response in demanding applications
Sound Isolated Operator panel
Improved operator comfort
Cat Connect
Remote monitoring for fleet management and asset tracking
Factory designed, built and tested
Single-source Supplier
World Wide Product Support
Supported by an industry leading global dealer network
Worldwide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Improved transportability
Lifting frame, 4 point lift and trailers
Power Distribution
Distribution sockets
Additional options
Synchronising controls.
Extended Service interval kits
600V generator
208V 3-phase NEMA Sockets
Retail Optimised
Option for open genset to meet Retail customer needs
Standard Equipment:
-
- Cat C7.1 Diesel Engine
-
- Heavy-duty.
Turbocharged.
After treatment
- Heavy-duty.
-
- Generator
-
- LC5034H Frame
-
- Control Panel
-
- Digital EMCP4.2B set mounted controller
-
- Cat Connect Remote Monitoring
-
- Provides package monitoring and management
-
- Cooling System
-
- Package mounted radiator with vertical air discharge.
Filled from factory
- Package mounted radiator with vertical air discharge.
-
- Charging / Starting System
-
- 12V heavy duty starting motor and charging alternator c/w battery isolator
-
- Fuel System
-
- 24 hour dual wall fuel tank with 3 way directional valve for external supply
-
- Air Filter
-
- Cyclonic/paper with dust cup and service indicator
-
- Distribution
-
- Single, robust enclosure for controls and distribution c/w 4 pole circuit breaker and safety cut off
-
- Structure
-
- Heavy Duty steel base frame with integral fuel tank.
Lifting frame and 4 point lift.
base frame is wider than enclosure to protect generator set during transportation
- Heavy Duty steel base frame with integral fuel tank.
-
- Enclosure
-
- Sound attenuating, galvanised steel enclosure with exceptional noise reduction performance
-
- Exhaust
-
- Integrated spark arresting silencer
-
- Lube Oil
-
- On engine primary and secondary oil filters. Filled from factory
-
- General
-
- Factory tested and inspected