XQ1140 Rental Power Generator Set.
Generator Set | |
Rating Prime | 910 ekW (1136 kVA) |
Frequency | 60 Hz |
Voltage | 120 - 600V |
Rating Standby | 1000 ekW (1250 kVA) |
Engine | |
Engine | Cat C18 |
Fuel | Diesel |
Dimensions | |
Height - Without Trailer | 114 in |
Length - Without Trailer | 480 in |
Width - Without Trailer | 96 in |
Weight with Lube Oil and Coolant, Without Trailer | 50107 lb |
Fuel Consumption | |
100% Load 60Hz | 66.4 gal/hr |
75% Load 60Hz | 52.4 gal/hr |
50% Load 60Hz | 38 gal/hr |
100% Load 60Hz | 71.8 gal/hr |
75% Load 60Hz | 56.6 gal/hr |
50% Load 60Hz | 41 gal/hr |
Noise rating (with enclosure) | |
Sound Power @ 7 meters (23 feet) @ All Ratings | 76 dB(A) |
Rental ready
Robust, durable product with a range of rental ready features to meet job requirements and applications.
Fuel/Emissions Strategy
Meets U.S. EPA Tier 4 Final emission standards and CARB certified for non-road mobile applications at all 60 Hz ratings.
Cat C18 Diesel Engines
Dual Cat C18 ACERT™ heavy-duty diesel engines.
Industry proven reliability.
CAT EMCP 4.4 Digital Controls
Dual EMCP 4.4 easy to use digital controls with manual and automatic paralleling capability.
Cat LC Series Generators
Class H Insulation.
Integrated voltage regular for fast response in demanding applications.
HMI Controls
Externally Mounted Color Touch-Screen HMI Control Center
Cat Connect
Remote monitoring for fleet management and asset tracking
Sound Attenuated Container
77 dBA @ 7m Sound Performance @ 75% Prime Load.
40' ISO high cube container, 9-high stack CSC certified Service and Personnel doors.
Externally-accessible controls
500 hr oil change intervals
Reducing operating costs and producing less waste
Reduced Environmental Impact
110% Spill Containment of On-Board Engine Fluids.
Factory designed, built and tested
Single-source Supplier
Worldwide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Additional options
Two-axle, air-ride traler with anti-lock brakesystem
Extended Service interval kits
600V generator
Standard Equipment:
-
- Cat C18 Diesel Engines
-
- Two Cat C18 Diesel Engines
- Reliable, rugged, durable design
- EPA Tier 4 Final and CARB Emissions Certified
- Turbocharged Aftercooled
- Aftertreatment module. DEF System
-
- Alternator And Alternator Attachments
-
- 3 Phase, brushless, 12 lead, Permanent Magnet Excited
- LC6134G Frame
- Anti-condensation space heaters
- Integrated voltage regulator (IVR) with VAR/PF control
- Sized for 105°C temperature rise at 40°C ambient
-
- Control Panels
-
- Dual EMCP 4.4 genset mounted digital controllers
- Externally accessible Color Touch-Screen HMI Control Center
- Manual and automatic paralleling capability
-
- Governing System
-
- Electrical governing system ADEM™ A4
-
- Cat Connect Remote Monitoring
-
- Provides package monitoring and management
-
- Cooling System
-
- Vertically mounted radiator with vertical airdischarge from the container
- Provides 47°C ambient capability at Prime rating
-
- Charging / Starting System
-
- UL Listed and CSA Certified 240V, 20 Amp battery charger
- Charging alternator; 24V-80A, heavy duty withintegral regulator and belt guards
- Solar maintainer for batteries
- Single electric starting motor, 24V per engine
-
- Fuel System
-
- 630-gal (2385 L) double-wall fuel tank, UL 142and ULC 601 Listed and complies with Transport Canada requirements, internal and external fuel fill
- Fuel tanks connected by fuel transfer system withfilter to allow both engines access to all fuel on-board
- Primary and secondary fuel filters
- Fuel cooler
-
- Air Inlet System
-
- Heavy-duty air element, canister type
-
- Distribution
-
- Externally accessible, Vibration Isolated, 3600A Frame, 1000 Ka, IC, 3-pole electrically operated breaker with lock out tag out provision
- Busbar connections
- Dual customer connections
-
- Sound Attenuated Container
-
- 40' ISO high cube container
- Sound level is 76 dB(A) at 7 meters per SAEJ1074 measured at 75% prime load
- Sound attenuated air intake louvers and fivelockable personnel doors with panic release
-
- Lube System
-
- Pump, integral oil cooler, lube oil, filter, filler and dipstick, and oil sampling valve
- Oil drain line with internal brass ball valve routedto connection point accessible from exterior
-
- General
-
- Factory tested and inspected
- Full manufacturer's warranty
- UL, NEMA, ISO, and IEEE standards
Optional Equipment:
-
- Trailer
-
- Two-axle, air-ride chassis with anti-lock brake system