Technical Specifications
Benefits and Features
Equipment
360 View
| Generator Set Specifications | |
| Continuous Rating | 2300 ekW @1.0pf |
| Fuel Type | Natural Gas, Biogas, Coal Gas, Hydrogen Blend (up to 25%) |
| Maximum Electrical Efficiency | 45.00% |
| Maximum Standby Rating | 2300 |
| Frequency | 50/60 Hz |
| RPM | 1500 rpm |
| Engine Specifications | |
| Engine Model | CG170B-20 |
| Aspiration | TA |
| Bore | 6.7 in |
| Stroke | 7.7 in |
| Generator Set Dimensions | |
| Length | 258 in |
| Width | 67 in |
| Height | 89 in |
| Dry Weight - Genset | 47377 lb |
High Efficiency, Lower Operating Costs
- Up to 45% electrical efficiency with Natural Gas
- 43.6% electrical efficiency with biogas
- Electrical output up to 2,300 kWel
- Reduced vibration and stress on components
Compact Size, High Profitability
- Compact design that delivers up to 15% more power output at the same size as its predecessor
- Long maintenance intervals (up to 80,000 hours)
- Available in different applications, such as natural gas, biogas, wellhead- and propane gas operation
- Maximum flexibility through different engine variants
Optimized Lubrication Consumption
- Consumes ~0.15g/kWh
- Reduced lube oil temperature through better cooling performance
- Savings of up to 3,000 liters of lube oil per year compared to comparable gensets
Standard Equipment:
-
- Air Cleaner
-
- Turbocharger with a water-cooled bearing case
- 2 Single-stage, single-element intake air filters with service indicator
-
- Cooling System
-
- Flange connections for all fluids VG-type or ISO-flanges
-
- Exhaust System
-
- PEARL/Low resistence exhaust system
- Exhaust wastegate
- Closed crankcase ventilation system
-
- Fuel System
-
- Electronic fuel metering valve
- Independently controlled cylinder monitoring and ignition system
- Pre-chamber spark plugs
- Zero pressure & Pre pressured gas train
-
- General
-
- External free standing combustion air preheating unit
-
- Lubrication
-
- Electric prelubrication pump
- Electric preheating
-
- Protection System
-
- Explosion Relief Valves
- Flame Arresters
-
- Starting/charging
-
- 24V starting motors
- Battery disconnect switch
-
- Attachments
-
- Anti-condensation space heater
- Busbar connections: left or right
- Winding temperature detectors
- 3-phase sensing and KVAR/PF control
- Reactive droop
- Anti-condensation space heater
-
- Control Panel
-
- TPEM (Total Plant & Energy Management System)
-
- Vibration Isolators
-
- Spring Isolators
-
- Certifications
-
- 2006/42/EC & 2006/95/EC, Declaration of Incorporation, Eurasian Conformity (EAC), Turkey certification, Ukraine certification, Nigeria Soncap certificate, Uzbekistan certificate (all 50 Hz only)
Optional Equipment:
-
- Cooling System
-
- CHP Module
- Electrical jacket water and aftercooler coolant pump
- Stainless steel mixture cooler
-
- Exhaust System
-
- Optional Exhaust Muffler
- SCR-System
-
- Fuel System
-
- Gas treatment
- Gas analysis device
- Low Heating Value (LHV) Intake Air Throttle Flap System - for gas with less than 4 kWh/mN^3 heating value. (50 Hz only)
-
- General
-
- Crankshaft vibration damper and guard
-
- Lubrication
-
- Base frame with extended lubrication oil volume
- 24V - Lubrication pump option
-
- Attachments
-
- Generator RTD module
- Neutral Ground - LV
- Cross-Current CT - HV
- Differential CTs - HV
- PTs - HV
-
- Vibration Isolators
-
- Seismic Isolators
-
- Certifications
-
- 50 Hz Grid Code