Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
| Generator Set Specifications | |
| Standby Rating | 350 ekW |
| Frequency | 60 Hz |
| Emissions/Fuel Strategy | U.S. EPA Tier 3 Certified |
| Voltage | 480 to 600 Volts |
| Speed | 1800 rpm |
| Duty Cycle | Standby |
| Engine Specifications | |
| Engine Model | Cat® C13 In-line 6, 4-cycle diesel |
| Compression Ratio | 16.3:1 |
| Aspiration | Turbocharged Air-to-Air Aftercooled |
| Fuel System | MEUI |
| Governor Type | ADEM™A4 |
Cat Generator Set Package
- Cat generator set packages have been fully prototype tested
- Meets NFPA 110 loading requirements
- Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
- Reliable, rugged, durable design
- Field-proven in thousands of applications worldwide
- Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
Alternator
- Superior motor starting capability minimizes need for oversizing alternator
- Designed to match performance and output characteristics of Cat diesel engines
- Robust Class H insulation
GCCP 1.2 Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
Cooling System
- Designed to operate in standard ambient temperatures up to104°F (40°C)
- Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
Designed to meet applicable global standards including ISO 8528, ISO 3046 and IEC 60034-1, with CSA, UL2200, IBC, NEMA and NFPA conformity available depending on configuration and market.
One Safe Source
- Components used in the generator set are selected based on seamless design integration to provide the optimum performance
- The generator set is fully assembled at a Caterpillar facility following our quality guidelines
- Each generator set package is tested before leaving the Caterpillar facility
- Cat product support, including dealer service, parts and warranty covers the entire Cat power system
Worldwide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Standard Equipment:
-
- Air Inlet System
-
- Air cleaner - Non canister, disposable
-
- Control Panel
-
- GCCP 1.2
-
- Cooling System
-
- Radiator sight gauge
- Blower fan and fan drive with guards
- Radiator, package mounted
- Coolant drain valve
- Thermostats and housing
- Jacket water pump, gear driven, centrifugal
-
- Exhaust System
-
- Exhaust manifold - dry
-
- Fuel System
-
- Engine fuel transfer pump
- Primary fuel filter w/integral water separator and secondary filter, spin on
- Fuel cooler
- Fuel priming pump
-
- Generators And Generator Attachments
-
- Brushless, self-excited 2/3 pitch (600V uses Internal excitation (IE))
- IP23 Protection
- Voltage regulator (single phase sensing)
- Insulation system, Class H
-
- Governing System
-
- Cat electronic governor (ADEM A4)
-
- Lube System
-
- Oil drain with valve
- Lubricating oil, CK-4 (10W-30)
- Oil filter, spin on
- Oil cooler
- Oil filler and dipstick
- Fumes disposal to front of radiator
- Shallow oil pan
-
- Mounting System
-
- Captive linear vibration isolators between base and engine-generator
- Includes lifting provisions and termination points for coolant and lube oil drain lines
-
- Protection
-
- Safety shutoff - High water temperature
- Safety shutoff - Low oil pressure
- Safety shutoff - Overspeed
-
- Starting/charging System
-
- 24-volt electric starting motor
- 24V, 45 Amp Charging alternator
-
- General
-
- Vibration damper
- Parts book
- Lifting eyes
-
- Telematics
-
- Cat® Product Link™ PL444 cellular
Optional Equipment:
-
- Bases, Mounting & Fuel Tanks
-
- Overfill prevention valve
- 5 Gallon Spill Containment
- Fuel tank pill pipe & lockable cap
- Integral / Extended tank base, 24 hours, UL142
- Audio & visual fuel alarm (@90% fuel level)
-
- Circuit Breaker
-
- Auxiliary contacts
- Single / Multi manual LSI
-
- Control System
-
- Volt free contacts
- Ground fault relay
- Audible alarm Gp
- Twist release, Red button emergency stop
- 20A GFCI (Ground Fault Circuit Interrupter)
- 100A Load center
- 16 -light NFPA 99/110 Annunciator
-
- Enclosures
-
- E-Stop
- Sound attenuated Level 2 enclosure (White)
- AC & DC Source lights
-
- Exhaust System
-
- Flexible exhaust connection
- Manifold and turbocharger guards
-
- Generator
-
- Space heater
- Permanent magnet excitation (PMG) generator
-
- Starting System
-
- Battery charger (UL Certified)
- Jacket water heater
- Standard battery set: 1000 CCA, 90 amp/hr.
- Oversize battery set, 1400 CCA, 200 amp/hr
-
- General
-
- UL2200 Certification
- CSA Certification
-
- Starting / Charging System
-
- Jacket water heater
- Battery disconnect switch