| Generator Set Specifications | |
| Standby Rating | 500/550/600/650/700/750 ekW |
| Prime Power Rating | 455/500/545/600/635/680 ekW |
| Emissions/Fuel Strategy | U.S. EPA Tier 2 / Tier 4 Certified |
| Voltage | 208 to 600 Volts |
| Frequency | 60 Hz |
| Speed | 1800 rpm |
| Duty Cycle | Standby, Prime |
| Engine Specifications | |
| Engine Model | C18 ATAAC, I-6, 4-Stroke Water-Cooled Diesel |
| Bore | 5.71 in |
| Stroke | 7.2 in |
| Displacement | 1106.4 l |
| Compression Ratio | 14.5:1 |
| Aspiration | Air to Air Aftercooled |
| Fuel System | Electronic unit injection |
| Governor Type | Adem™A4 |
| Generator Set Dimensions | |
| Length - Maximum | 5550 in |
| Width - Maximum | 80.9 in |
| Height - Maximum | 107.8 in |
Cat Generator Set Package
- Cat generator set packages have been fully prototype tested
- Accepts 100% block load in one step and meets NFPA 110 loading requirements
- Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
- Reliable, rugged, durable design
- Field-proven in thousands of applications worldwide
- Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
Alternator
- Superior motor starting capability minimizes need for oversizing alternator
- Designed to match performance and output characteristics of Cat diesel engines
- Robust Class H insulation
GCCP Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
Cooling System
- Designed to operate in standard ambient temperatures up to 50°C (122°F)
- Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
Designed to meet applicable global standards including ISO 8528, ISO 3046 and IEC 60034-1, with CSA, UL2200, IBC, NEMA and NFPA conformity available depending on configuration and market.
One Safe Source
- Components used in the generator set are selected based on seamless design integration to provide the optimum performance
- The generator set is fully assembled at a Caterpillar facility following our quality guidelines
- Each generator set package is tested before leaving the Caterpillar facility
- Cat product support, including dealer service, parts and warranty covers the entire Cat power system
World Wide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Standard Equipment:
-
- Air Inlet
-
- Standard light duty air cleaner
-
- Air Inlet System
-
- Turbocharger with Aftercooler
-
- Cooling
-
- Caterpillar extended life coolant
- Fan drive, battery charging alternator drive
- Coolant drain line with valve
- Radiator and cooling fan with guard
- Package mounted radiator
-
- Exhaust
-
- Exhaust flange outlet
-
- Exhaust System
-
- Stainless steel exhaust flex gaskets, raincap and SAE exhaust flange for customer use - shipped loose
-
- Fuel System
-
- Standard narrow skid base
-
- Fuel
-
- Primary fuel filter with integral water separator
-
- Generator And Attachments
-
- Current transformers
- Power center, IP22
- Integrated voltage regulator (IVR)
- Mandatory option circuit breaker, IEC, 3 pole, mounted in power centre
- Automatic voltage regulator (AVR)
-
- Power Termination
-
- Busbar
-
- Control System
-
- GCCP 1.2
-
- Governing System
-
- Cat electronic governor (ADEM A4)
-
- Lube System
-
- Lubricating oil
- Oil drain valves
-
- Mounting System
-
- Captive linear vibration isolators
-
- Mounting
-
- Rubber vibration isolators
-
- Starting/charging
-
- Starter motor
-
- General
-
- Engine and alternator pre-paint, Caterpillar yellow
- Paint - Caterpillar yellow except rails and radiators gloss black
-
- Telematics
-
- Cat® Product Link™ PL444 cellular
Optional Equipment:
-
- Air Inlet System
-
- Dual element air cleaner
- Heavy duty air cleaner
-
- Exhaust
-
- Industrial, residential, critical mufflers
-
- Power Termination
-
- Circuit breakers, UL listed
-
- Circuit Breakers
-
- Single/Dual/Third circuit breakers
-
- Control Panels
-
- Load share module
- Local & remote annunciator modules
- Digital I/O module
-
- Control System
-
- Local alarm modules
- Remote annunciator module
- Oil temperature displays
- GCCP 1.5
-
- Control Panel
-
- EMCP 4.4 Genset controller
-
- Cooling System
-
- Low coolant temperature alarm
- Radiator duct flange
-
- Enclosures
-
- Sound Attenuated / Weather Protective / Cold Weather
-
- Starting/charging
-
- Jacket water heater
- Standard battery
- Charging alternator
-
- Exhaust System
-
- 8 and 10 inch GP flanges
- 8 and 10 inch elbow kits
- Engine mounted muffler
- Manifold and turbocharger guards
-
- Fuel System
-
- Integral tank base
- Sub base fuel tank
- Michigan tank kit bundle
-
- General
-
- CSA Certification
- Automatic transfer switches (ATS)
- The following options are based on regional and product configuration:
- UL 2200 package
- Single or dual wall integral fuel tanks
- IBC seismic certification
- Narrow, wide or skid base
-
- Generator And Attachments
-
- Space heaters
- Permanent magnet excitation (PMG)
- LC frame generator with CIP
- Ingress protection
- Cold weather bundle
- LC frame oversize generators
-
- Lube System
-
- Manual sump pump
-
- Starting And Charging
-
- Battery disconnect switch
- Jacket water heaters
- 5A Battery charger