The ATC-300+ is a comprehensive and multifunctional microprocessor-based ATS controller. It is a compact and self-contained panel-mounted device that is designed to replace traditional relay and solid-state logic panels. The ATC-300+ Controller provides programmed flexibility to address the needs of any system. It operates from all system voltages between 120 to 600V, single-phase and three-phase at 50 or 60 Hz. In addition, a period of no control power is provided. The controller monitors the condition of the three-phase line-to-line voltage and frequency of Source 1 and Source 2 power sources and can be programmed for single-phase operation. The ATC-300+ Controller provides the intelligence to ensure that the ATS operates properly through a series of programmed sensing and timing functions.
Technical Summary | |
Rating Range | 120 to 600V, single phase and three phase @ 50/60 Hz |
Transfer Type | Switch application dependent |
Switch Type | Switch application dependent |
ATC Controller Specifications | |
Input Control Voltage | 65 to 145 Vac 50/60 hZ |
Voltage Measurements of Utility | Source 1 VAB Source 2 VAB Source 1 VAC Source 2 VBC Source 1 VCA Source 2 VCA |
Voltage Measurement Range | 0 to 790 VAC rms (50/60 Hz) |
Voltage Measurement Accuracy | +/-2% of nominal input voltage |
Frequency Measurements Of | Source 1 and Source 2 |
Frequency Measurement Range | 40 Hz to 70 Hz |
Frequency Measurement Accuracy | +/- 0.1 Hz |
Undervoltage Dropout | 50% to 90% of nominal voltage |
Undervoltage Pickup | (Dropout +2%) to 99% of the nominal system voltage |
Underfrequency Dropout Range | 90 to 97% of the nominal system frequency |
Underfrequency Pickup Range | (Dropout +1 Hz) to 99% of the nominal system frequency |
Overfrequency Dropout Range | 103 to 110% of the nominal system frequency |
Overfrequency Pickup Range | 101% to (dropout - 1 Hz) of the nominal system frequency |
Operating Temperature Range | -20 to 70 degree C (-4 to +158 degree F) |
Storage Temperature Range | -30 to 85 degree C (-22 to +185 degree F) |
Operating Humidity | 0 to 95% relative humidity (noncondensing) |
Operating Environment | Resistant to ammonia, methane, nitrogen,hydrogen and hydrocarbons |
Generator Start Relay | 5A, 1/6 hp @ 250 Vac Vac 5A @ 30 Vdc with a 150W maximum load |
K1, K2 Relays | 10A, 1-3 hp @ 250 Vac 10A@30 Vdc |
Applicable Testing | UL-recognized component Meets intent of UL 991 & UL 1008 Meets IEC 1000-4-2, 1000-4-3, 1000-4-4 |
Applicable Testing Continued | 1000-4-5, 1000-4-6, 1000-4-11 CISPR 11, Class A FCC Part 15, Class A CSS 22.2-178 |
Enclosure Compatibility | NEMA 1, NEMA 3R and NEMA 12 UV-resistant ATC-300+ faceplate |
Product Features
- Auxiliary relay contacts:
- Source 1 present 2NO and 2NC
- Source 2 present 2NO and 2NC
- Source 1 and source 2 sensing:
- Undervoltage / underfrequency
- Overvoltage / overfrequency
- Three-phase rotation protection
- Three-phase voltage unbalance/loss
- Pre-transfer signal contacts 1NO and 1NC
- Go to emergency (Source 2)
- Seven field-programmable time delays
- LCD-based display for programming, system diagnostic and help message display
- Mimic diagram with source available and connected LED indication
- Time-stamped history log
- System test pushbutton
- Programmable plant exercise (off, daily, 7,14 and 28 day) interval selectable run time 0-600 minutes no load/load with fail-safe
- Integral overcurrent protection (optional)
- In-phase transition
- Stainless steel cover for controller (optional)
- Communications via RS-232 or Modbus through an integrated RS-485 port (optional)