C4.4 Generator Set

.
🔍
🔍
🔍
🔍
🔍
🔍

 

Description
Technical Specifications
Benefits and Features
Equipment
360 View

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Generator Set Specifications
Standby Rating 40/50/60/80/100 ekW
Prime Power Rating 36/45/55/72/90 ekW
Emissions/Fuel Strategy U.S. EPA Tier 3 Certified / SCAQMD
Voltage 110 to 480 Volts
Frequency 60 Hz
Speed 1800 rpm
Duty Cycle Standby, Prime
Engine Specifications
Engine Model Cat® C4.4
Bore 4.1 in
Stroke 5 in
Displacement 268.5 in³
Compression Ratio 16.2:1, 17.25:1, 18.2:1 or 18.3:1
Aspiration Turbocharged
Fuel System Direct Injection or Common Rail
Governor Type Mechanical
Generator Set Dimensions
Length - Maximum 75.8 in
Width - Maximum 44.1 in
Height - Maximum 53.6 in

Cat Generator Set Package

        

  • Cat generator set packages have been fully prototype tested
  •     

  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  •     

  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine

        

  • Reliable, rugged, durable design
  •     

  • Field-proven in thousands of applications worldwide
  •     

  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

Alternator

        

  • Superior motor starting capability minimizes need for oversizing alternator
  •     

  • Designed to match performance and output characteristics of Cat diesel engines
  •     

  • Robust Class H insulation

GCCP 1.2 Control Panel

        

  • User-friendly interface and navigation
  •     

  • Scalable system to meet a wide range of installation requirement
  •     

  • Expansion modules and site-specific programming for specific customer requirements
  •     

  • Image may not be a representative of actual product

Cooling System

        

  • Designed to operate in standard ambient temperatures up to 50°C (122°F)
  •     

  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications

Designed to meet applicable global standards including ISO 8528, ISO 3046 and IEC 60034-1, with CSA, UL2200, IBC, NEMA and NFPA conformity available depending on configuration and market.

One Safe Source

        

  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  •     

  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  •     

  • Each generator set package is tested before leaving the Caterpillar facility
  •     

  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

World Wide Product Support

        

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  •     

  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Standard Equipment:

  • Air Inlet System
    • Catridge type air filter
  • Cooling System
    • Radiator and cooling fan with guards
    • Coolant drain line with valve
    • Fan drive, battery charging alternator drive
    • Caterpillar extended life coolant
  • Exhaust System
    • Stub pipe, gaskets, raincap and SAE exhaust flange for customer use - shipped loose
  • Generator
    • Automatic voltage regulator
    • 12 Leads
    • IP23 Protection
    • Circuit breaker, IEC, 3 pole, mounted in tower panel
    • Segregated low voltage (AC/DC) wiring panel
  • Lube System
    • Oil drain line with valve
    • Lubricating oil
  • Mounting System
    • Termination points for coolant and lube oil drain lines
    • Includes lifting provision and drag points
    • Captive linear vibration isolators
  • Starting/charging System
    • Standard battery
  • General
    • Engine and alternator pre-paint, Caterpillar yellow
  • Telematics
    • Cat® Product Link™ PL444 cellular

Optional Equipment:

  • Alternator System
    • Anti-condensation heater
    • LC Frame
    • LC Frame alternator with coastal insulation protection
  • Cooling System
    • Low coolant level shutdown
    • Coolant heater
    • Low coolant temperature alarm
  • Control Panel Options
    • Panel mounted audible alarm
    • Emergency stop with key
    • Battery charger
    • Overload shutdown via breaker
    • Voltage adjust potentiometer
  • Enclosures
    • Sound attenuated Level 1 / Level 2
    • Weather Protective
  • Fuel System
    • Low fuel level alarm
    • Skid base
    • Low fuel level shutdown
    • Sub base tanks
    • High fuel level alarm
  • Global Certifications
    • Certification for CIS
  • Mufflers
    • 10,25,35 dBA Mufflers
    • Muffler with enclosure
  • Mounting Options
    • External single point lift - enclosure
  • General - Accessories / Miscellaneous
    • Stone guards/rad trans flange


Related Equipment