Description
Technical Specifications
Benefits and Features
Equipment
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Generator Set Specifications | |
Frequency | 60 Hz |
Natural Gas Rating | 175 eKW |
Emissions/Fuel Strategy | U.S. EPA Certified for Stationary Emergency Application |
Speed | 1800 rpm |
Displacement | 14.17 in³ |
Fuel Type | Natural Gas |
Engine Specifications | |
Engine Model | G14.2L Spark Ignited |
Fuel System | Carburetor, Down Draft |
Aspiration | Turbocharged - Aftercooled |
Governor Type | Electronic |
Compression Ratio | 9.5:1 |
Bore | 5.31 in |
Stroke | 165.1 mm |
Generator Set Dimensions | |
Length | 3250 mm |
Width | 52.93 in |
Height | 1711.2 mm |
Weight | 2610.9 kg |
Engine
- Four-stroke-cycle gas engine combines consistent performance and excellent fuel economy with minimum weight
Generator
- Matched to the performance and output characteristics of Cat engines
- Industry leading mechanical and electrical design
- Industry leading motor starting capabilities
- High Efficiency
EMCP Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
Design Criteria
- The generator set facilitates compliance with NFPA 110 and meets ISO 8528-5 requirements for transient response
- Cooling system designed to operate in 50˚C/122˚F ambient temperatures with an air flow restriction of 0.5 in. water
UL 2200 / CSA - Optional
- UL 2200 Listed packages
- CSA Certified
- Certain restrictions may apply
- Consult with your Cat® Dealer
Worldwide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Standard Equipment:
-
- Coolant
-
- 50/50 Ethylene glycol antifreeze
- Factory-installed radiator
- Closed coolant recovery system
-
- Fuel
-
- Fuel pressure test po
- Primary and secondary fuel shut-off
- Low fuel pressure switch
-
- Generator
-
- Full load capacity alternator
- Permanent magnet excitation
- Class H insulation materia
-
- Controls
-
- EMCP 4.2 Series generator set controller
-
- Mounting
-
- Vibration isolaton (puck type)
-
- Starting / Charging
-
- Battery cables
- Battery charging alternator
- Solenoid activated starter motor
- Engine electrical system
Optional Equipment:
-
- Generator
-
- Thermal magnetic or electronic trip MCCBs
- Anti-condensation heater
- Shunt trip and auxiliary contact breaker
-
- General
-
- UL 2200 package
- Enclosures: sound attenuated (L1 or L2), weather protective
- CSA Certification
- Dual Element or Heavy Duty air cleaner