.
Description
Technical Specifications
Benefits and Features
Equipment
360 View
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Generator Set Specifications | |
Maximum Rating | 100 ekW |
Minimum Rating | 100 ekW |
Emissions/Fuel Strategy | U.S. EPA Cert., Tier 3 |
Voltage | 208 to 600 Volts |
Frequency | 60 Hz |
Speed | 1800 rpm |
Duty Cycle | Standby |
Engine Specifications | |
Engine Model | C4.4, In-line 4, 4-cycle diesel |
Bore | 4.1 in |
Stroke | 5 in |
Displacement | 269 in³ |
Compression Ratio | 16.7:1 |
Aspiration | Turbocharged |
Fuel System | Common Rail |
Governor Type | Mechanical, ADEM™A4 |
Generator Set Dimensions | |
Length - Maximum | 82.6 in |
Width - Maximum | 43.3 in |
Height - Maximum | 52.9 in |
Dry Weight - Genset (maximum) | 2222 lb |
Cat Generator Set Package
- Cat generator set packages have been fully prototype tested
- Accepts 100% block load in one step and meets NFPA 110 loading requirements
- Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
- Reliable, rugged, durable design
- Field-proven in thousands of applications worldwide
- Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
M-Frame Alternator
- Superior motor starting capability minimizes need for oversizing alternator
- Designed to match performance and output characteristics of Cat diesel engines
- Robust Class H insulation
GCCP 1.2 Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
Cooling System
- Designed to operate in standard ambient temperatures up to 55°C (131°F)
- Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
- UL 2200 Listed
- ULC Certification Available
One Safe Source
- Components used in the generator set are selected based on seamless design integration to provide the optimum performance
- The generator set is fully assembled at a Caterpillar facility following our quality guidelines
- Each generator set package is tested before leaving the Caterpillar facility
- Cat product support, including dealer service, parts and warranty covers the entire Cat power system
Worldwide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Standard Equipment:
-
- Air Inlet System
-
- Air cleaner; light duty with disposable element
- Air cleaner
-
- Cooling System
-
- Coolant drain line with valve
- Radiator and cooling fan with guards
- Caterpillar extended life coolant
- Fan drive, battery charging alternator drive
-
- Control Panel
-
- GCCP 1.2 Control panel
-
- Exhaust System
-
- Stub pipe, gaskets, raincap and SAE exhaust flange for customer use - shipped loose
-
- Fuel System
-
- Standard open set fuel tank/base supplied base, formed steel with single wall integral 24-hour fuel tank
-
- Generator
-
- Circuit breaker, IEC, 3 pole, mounted in tower panel
- IP23 Protection
- Tower panel, IP22, bottom cable entry
- 12 Leads
- Voltage regulator (single phase sensing)
- Segregated low voltage (AC/DC) wiring panel
-
- Governing System
-
- Mechanical and electrical governing system - model dependent
-
- Lube System
-
- Lubricating oil
- Oil drain line with valve
-
- Mounting System
-
- Termination points for coolant and lube oil drain lines
- Captive linear vibration isolators between base and engine-generator
- Includes lifting provision and drag points
-
- Starting/charging System
-
- Batteries
- 24V battery with rack and cables
-
- General
-
- Engine and alternator pre-paint, Caterpillar yellow
Optional Equipment:
-
- Alternator System
-
- Anti-condensation heater
- 3 phase sensing
- Permanent magnet excitation (PMG)
- R Frame auxilliary winding
- Quadrature droop kit
-
- Circuit Breakers
-
- Circuit breaker upgrades - 4 Pole circuit reaker to 250A, 400A and 630 A
-
- Cooling System
-
- Coolant heater
- Low coolant temperature alarm
- Low coolant level shutdown
-
- Control Panel Options
-
- Earth fault (2 wire only)
- Control panel heater
- GCCP 1.2 Control panel
- Volt free contacts
- Emergency stop with key
- Voltage adjust potentiometer
- Overload shutdown via breaker
- Panel mounted audible alarm
- Battery charger
- Earth leakage (2 wire only)
- Speed adjust potentiometer
-
- Enclosures
-
- Sound attenuated Level 2 enclosure
-
- Fuel System
-
- Low fuel level alarm
- Bunded fuel tank
- Low fuel level shutdown
- High fuel level alarm
-
- Mounting Options
-
- Battery removal
- Electronic governor
- Industrial silencer
- External single point lift - enclosure
- Silencer installation kit
-
- Special Packing/inspectons For Shipment
-
- PGS Test report @ 0.8 power factor
- PGS Test report @ 1.0 power factor
-
- General - Accessories / Miscellaneous
-
- Packing case - canopied set
- Packing case - compact set
- Stone guards/rad trans flange